NAVAT Automatic Intelligent CT PT Calibration Tester

Product Detailed Description

NAVAT Automatic Intelligent CT PT Calibration Tester

Product introduction

It is a new automated testing equipment, it uses advanced electronic technology, the transformer is taken directly polar decomposition of the error signal, and after appropriate after the operation, the transformer points, phase error , quadrature error in the digital display. NAVAT transformer calibrator is simple, intuitive readings, measure quickly, can reduce energy consumption, reduce labor intensity; small size, light weight, easy to carry and field testing; instrument can be fixed at 5% Operating current (voltage) under testing; some old users asked Nanao Electric Wuhan Co., Ltd. produce this new generator testers, which can detect S-class current transformer and the secondary voltage of the voltage transformer calibrator 100/3V, then 1% of the rated instrument can measure the current transformer operating current the error; instrument in the detection process can be easily carried from the school at any time to ensure the accuracy of the instrument; critical components using imported components, stable and reliable quality, widely used in metering, power supply and other departments and transformer manufacturers, is to carry out transformer testing the ideal instrument.

Also called name

Transformer tester, PT calibrator, CT calibrator,NAVAT Automatic Intelligent CT PT Calibration Tester

The Characteristics of the products

1. Use 320x240 dot-matrix LCD, with wide station visual zone and long life back lighting, easy to use.

2. With beautiful appearance.

3. Percentage, ratio, phase-angle difference displayed in big characters, convenient for customers to test.

4. Meets JJG314-1993 and JJG314-1994,automatically sample.

5. Automatically detect the polarity and ratio error.

6. The soft ware of the upper-computer with the function of virtual instrument.

7. Solve the problem of S degree measurement.

8. Automatically change the measurement distance.

9. Use advanced, special circuit and DSP technique, solve the problem of instability of resistor-condenser & phase-shifted Circuit

10. Power consumption: < 15VA(without micro printer)

                       < 25VA(with micro printer)

11. Harmonic Reduction:> 40db

12. Dimension:260mm×350mm×150mm

13. Weight:6kg

The parameters of the products 

1. service condition

   (1) temperature:5--40℃   humidity:<80%(25)  

       altitude:<2500m

       power frequency:50Hz±0.5 Hz    supply voltage:220V±5V

   (2) measurement range:

       co-phase component (%): 0.0001200.0                  

       resolution: 0.0001

       orthogonal component: 0.001~700.0         resolution: 0.001

       resistance(Ω): 0.0001~20.0               resolution: 0.0001

       admittance (ms): 0.0001~20.0              resolution: 0.0001

   (3) intrinsic error:

       co-phase component:   ΔX=±(X×2%Y×2%)± Dx (1degree optional)

       orthogonal component: ΔY=±(X×2%Y×2%)± Dy (1degree optional)

                            “X,Y”——display of the device

                            “Dx , Dy”—— the quantization error of the device

                             Dx=2,Dy=5

   (4) dial indicator:      2 degree (1degree optional)

2. working range:

  (1) current:(1%149%)In    (In =5A)

              (5%149%)In    (In =1A)

  (2) voltage:(5%149%)Un    (Un =100V150V100V/ )

              (5%149%)Un    (Un =100V/3)

3. working load:  

  (1) current:TO-TX0.12Ω       cosΦ=1

  (2) voltage:a-x0.25VA        (100V)

4. polarity error indication

There should be polarity error indication when the working current (voltage) exceeds 5% of the rated current (voltage) , or the error more than 180%.

Note: if there was not indication when the working current (voltage) is more than 10% of the rated current (voltage), please stop increasing the current (voltage ), to avoid burn the device.

5. ratio error indication:

There should be ratio error indication when the working current (voltage) exceeds 5% of the rated current (voltage) , or the error more than 30% but less than 180%.

6. explanation for insulation and withstand tests:  terminal TX connects to ( )terminal

 the outlet can bear the shell 1.5kV, 1.5min withstand voltage.

7, transformer calibrator main features:

use 320 x 240 dot matrix LCD, visible range, with a long-life back light, easy to use;

English user interface, attractive interface;

dial indicator, ratio difference, angle difference using large font display, user observation;

fully meet JJG314-1993 and JJG314-1994 requirements, automatic sampling;

automatically determine the polarity of the error, ratio error;

PC software with virtual instruments open function;

completely solve the S-class measurement problems;

auto ranging;

unique circuitry and advanced DSP technology combine to completely remove the RC phase shifter circuit instability.

power consumption: <15VA (without micro-printer)

<25VA (with micro-printer)

harmonic rejection ratio:> 40db

Dimensions: 260mm (length) × 350mm (W) × 150mm (height)

Weight: 6kG

 

NACT type CT ratio polarity tester

Product Photo

  • click for larger image
  • Click this to view the 'NAVAT Automatic Intelligent CT PT Calibration Tester' of the large image 1.

Company Detailed

Manufacture equipment include:
-- SF6 circuit breaker and GIS; 
-- Oil-Immersed (No Pd) Test Transformer
-- Automatic Insulating Oil Dielectric Tester
-- Partical Discharge/High Voltage Withstand Device
-- 5kA-500kA Impulse Current Generator
-- 10-7200kV Impulse Voltage Generator;
-- Microcomputer Relay Protection Tester;
-- CT, PT, CVT;
-- Voltage Divider/High Voltage Measuring Device/Six Phases Tester;
-- Measurement Product/Secondary Circuit Tester;
-- Cable/Circuit/Lightning Arrester Test Device;
-- Earthing/Insulation/SF6 Gas Detection;
-- Transformer Inspection/Switch Testing Device;
For now, we have finish several big abroad bidding of turn-key project on above field.